GE GL 311 F3/4031 P/VE Operating Instructions Manual page 101

High voltage circuit breaker
Hide thumbs Also See for GL 311 F3/4031 P/VE:
Table of Contents

Advertisement

CAUTION
REV7
/REV7
Reassembly:
• Replace all O-rings and gaskets.
• Reverse the sequence to assemble the crankcase.
• Insert a new filter bag (see "Replacing the Adsorption filter"
on Page 97).
The following instructions must be followed when assembling
and installing the parts:
- Follow the specified lubrication procedure.
- Replace all seals and gaskets.
- Tighten the three screws (68) to a torque of 18Nm.
- Do not forget the filter sleeve (48).
- Do not install a new filter bag until right before evacuating the
assembled pole column.
• Mount
the
interrupter
Interrupter Chamber to the Post Insulator" on Page 95).
• Remount the pole column on the base frame.
• Re-commission the circuit breaker as described in the
commissioning section.
OI 250 (EN)
R
ECONDITIONING
chamber
(see
"Connecting
the
101 / 146

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gl 312 f3/4031 p/ve

Table of Contents