Mounting the Connecting Brackets

REV7
/REV7
Lattice supports are connected with one another by connecting
brackets. Note the positions of the oblong hole and the guide hole
in the connecting brackets (views X, Y and Z).
• Position the connecting bracket (1) between poles A and B on the
horizontal strut (views T and U).
• Fasten the bracket to pole B via the guide hole (view Y) using the
bolt (2), washer (4) and nut (5) (view U).
• Fasten the bracket to pole A via the oblong hole (view X) using
the bolt (2), washer (4) and nut (5) (view T). Tighten to a torque of
202 Nm.
• Position the connecting bracket (1) between poles B and C on the
mounting flange for the pole columns (views V and W).
• Fasten the bracket to pole C via the guide hole (view Z) using the
bolt (3), washer (4) and nut (5) (view W).
• Fasten the bracket to pole B via the oblong hole (view Y) using
the bolt (3), washer (4) and nut (5) (view V). Tighten to a torque of
202 Nm.
The correct center-to-center distance between poles is achieved
when the connecting brakkets are mounted as shown in views X, Y
and Z.
OI 250 (EN)
I
NSTALLATION
33 / 146