Toshiba MMY-MUP0721FT6P-UL Service Manual page 94

Table of Contents

Advertisement

DN
Item
01d
System cooperation
defrosting settings 1
(number cooperating)
01E
System cooperation
defrosting settings 2
(zone address)
01F
System cooperation
defrosting settings 3
(cooperation address)
03d
Existence of Automatic Back Up
03F
Operation Control during Overflow
Detection of Indoor Unit
040
Operation Control during Outside
Abnormal Input Switching control
in receiving [L30][L02] from indoor)
055
Cooling priority control below 5F
Heating unit fan mode restriction
058
during individual defrosting
082
Communication setting
High Heating mode setting
0C6
Available only for standard model
0000 : None (vassal)
0002 : 2-system cooperation (master unit)
* set [01D] = 0002 or 0003 to outdoor unit set to master unit in outdoor DN code [01F]
0000 : None
0001 when not using central controller for control for system cooperation defrosting,
0001 to 0128 when using central controller
0000: None
0002 or 0003: Vassal units 2 or 3
0000 : Provided
0000 : System abnormal stop
0000 : System continuous operation
(Stop the corresponding indoor unit.)
0000:Heating priority(Def)
*Heating operation requests are ignored below 5F.
0000:Usual
0000: TCC-Link
0000: Normal mode
- 94 -
Description
0001 : Prohibition
0003 :
3-system cooperation (master unit)
0001 to 0128: Addresses
0001: Master unit
0001 : Not provided
0001 : System continuous operation
(Stop the corresponding indoor unit.)
0001 : System abnormal stop
0001:Cooling priority*
0002:Heating unit fan mode restriction
0003 : TU2C-Link
0001 : High heating mode
At shipment
0000: None
(vassal)
0000: None
0000 : None
0000 : Provided
0000 : System
abnormal stop
0000 : System
continuous
operation
(Stop the
corresponding
indoor unit.)
0000
0000: Usual
0000: TCC-Link
0000:Normal mode