Next, enter the total length for each liquid pipe diameter in the following table, and then calculate the additional
amount of refrigerant by pipe length.
Table 2. Additional amount of refrigerant based on the liquid pipe and length.
Pipe diameter on the
liquid side
1/4"
3/8"
1/2"
5/8"
3/4"
7/8"
Table A. Correction factor on indoor unit capacity type.
Connection rate
Factor
Less than 135 %
135 % or more
Then refer to following table below, calculate corrective amount of refrigerant according to indoor unit
capacity (C).
Table 3. Correction factor on indoor unit capacity type
Table 3-1. Additional amount of refrigerant for standard indoor unit type
Indoor unit
Capacity code
capacity type
007
7.5
009
9.5
012
12
015
15.4
018
18
021
21
024
24
027
27
030
30
036
36
042
42
048
48
054
54
072
72
096
96
※ If the outside air unit type (MMD-UP***1HFPUL) is connected, The additional amount refrigerant for outside air
unit type is 0 lbs.
Standard amount
Total pipe length on
of refrigerant
each liquid side
lbs/ft
0.017 ×
0.037 ×
0.071 ×
0.108 ×
0.168 ×
0.235 ×
1.3
1.2
Corrective amount
of refrigerant
lbs
0.44
0.88
1.32
2.20
Additional amount of refrigerant
pipe diameter on each liquid side
ft
  =
  =
  =
  =
  =
  =
Number of connected
Corrective amount of refrigerant
indoor units
Number
- 122 -
lbs
  lbs
  lbs
  lbs
  lbs
  lbs
  lbs
on each indoor unit capacity
lbs
=
bs
=
bs
=
bs
=
bs
=
bs
=
bs
=
bs
=
bs
=
bs
=
bs
=
bs
=
bs
=
bs
=
bs
=
bs