Table 2.Additional amount of refrigerant base on the liquid pipe and length.
Liquid pipe diameter
Additional amount of refrigerant
Table A. Correction factor on Indoor connection capacity
Diversity
Less than 135 %
135 % or more
Table 3.Additional amount of refrigerant based on the indoor unit capacity type and number
Table3-1.Additional amount of refrigerant for standard indoor unit capacity type.
Indoor unit capacity type
Additional amount of refrigerant
Table3-2. Additional amount of refrigerant for 4-way Cassette type (Model name: MMU-UP***1HP-UL).
Indoor unit capacity type
Additional amount of refrigerant
Table3-3. Additional amount of refrigerant for Concealed Duct Standard type (Model name: MMD-UP***1BHP-UL).
Indoor unit capacity type
Additional amount of refrigerant
Table3-4. Additional amount of refrigerant for DX Coil inter face (Model name: TCB-IFDMR01UP-UL / RBM-A***1UPVR-UL).
Indoor unit capacity type
Additional amount of refrigerant
If the Outside Air Unit (MMD-UP****HFP-UL) is connected, the correction amount refrigerant for Outside Air Unit is o kg.
Table 4.Refrigerant amount adjustment based on indoor unit connection capacity.
Refrigerant amount adjustment
Diversity
D
lbs
50 % ≤ D < 60 %
-9.92
60 % ≤ D < 70 %
-7.72
70 % ≤ D < 80 %
-5.51
80 % ≤ D < 90 %
-3.31
90 % ≤ D < 95 %
-1.10
95 % ≤ D
Charging of refrigerant
Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the liquid side.
If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and gas sides,
operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas side. In this time, choke
the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
lbs / ft
kg / m
Correction factor
1.3
1.2
007
009
0.44
lbs /unit
0.2
kg / unit
007
009
0.44
lbs /unit
0.2
kg / unit
007
009
lbs /unit
kg / unit
007
009
012
ton
0.6
0.8
1
lbs /unit
0.24
0.32
0.42
kg / unit
0.11
0.15
0.19
kg
-4.5
-3.5
-2.5
-1.5
-0.5
0
0
1/4 in.
3/8 in.
1/2 in.
6.4 mm
9.5 mm
12.7 mm 15.9 mm 19.1 mm 22.2 mm
0.017
0.037
0.071
0.025
0.055
0.105
012
015
018
021
024
0.88
0.4
012
015
018
024
027
0.88
0.4
012
015
018
021
024
0.88
0.4
015
018
024
027
030
1.25
1.5
2
2.25
2.5
0.60
0.72
0.92
1.12
1.20
0.27
0.33
0.42
0.51
0.54
- 20 -
5/8 in.
3/4 in.
7/8 in.
0.108
0.168
0.235
0.160
0.250
0.350
027
030
036
042
048
054
1.32
0.6
030
036
042
048
054
1.32
0.6
030
036
042
048
054
1.32
0.6
036
048
054
060
072
3
4
4.5
5
1.51
1.91
2.11
2.50
3.09
0.69
0.87
0.96
1.13
1.40
072
096
2.20
1.0
096
120
6
8
10
3.97
4.68
1.80
2.12