Toshiba MMY-MUP0721FT6P-UL Service Manual page 212

Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Controller
Check
Sub-code
code
1∗: Compressor
1 side
2∗: Compressor
2 side
H01
H01
1∗: Compressor
1 side
H02
H02
2∗: Compressor
2 side
1∗: Compressor
1 side
2∗: Compressor
H03
H03
2 side
H05
H05
H06
H06
H07
H07
Location
Description
System status
of
detection
Compressor
Compressor
All stop
P.C. board
breakdown
Compressor
Compressor
All stop
P.C. board
trouble (lockup)
Compressor
Current
All stop
P.C. board
detection
circuit trouble
I/F
TD1 sensor
All stop
miswiring
(incomplete
insertion)
I/F
Activation of
All stop
low-pressure
protection
I/F
Low oil level
All stop
protection
- 212 -
Check code detection
Check items (locations)
condition(s)
Inverter current detection
Check power supply
circuit detects overcurrent
voltage.
and shuts system down.
Check for failure in
compressor.
• Check for possible cause
of abnormal overloading.
• Check for failure in outdoor
P.C. board (Compressor).
Overcurrent is detected
• Check for failure in
several seconds after
compressor.
startup of inverter
• Check connection of
compressor.
connectors/terminals on
compressor P.C. board.
• Check conductivity of case
heater.
(Check for refrigerant
problem inside
compressor.)
Current flow of at least
• Check current detection
specified magnitude is
circuit wiring.
detected despite inverter
• Check failure in outdoor
compressor having been
P.C. board (Compressor).
shut turned off.
Discharge temperature of
• Check installation of TD1
compressor 1 (TD1) does
sensor.
not increase despite
• Check connection of TD1
compressor being in
sensor connector and
operation.
wiring.
• Check resistance
characteristics of TD1
sensor.
• Check for failure in outdoor
P.C. board (I/F).
Low-pressure Ps sensor
• Check service valves to
detects operating pressure
confirm full opening
lower than 0.02MPa.
(both gas and liquid sides).
• Check outdoor PMVs for
clogging (PMV1, 2, 3).
• Check for failure in SV4
circuits.
• Check for failure in low-
pressure Ps sensor.
• Check indoor filter for
clogging.
• Check valve opening
status of indoor PMV.
• Check refrigerant piping for
clogging.
• Check operation of outdoor
fan (during heating).
• Check for insufficiency in
refrigerant quantity.
Operating compressor
<All outdoor units in
detects continuous state of
corresponding line to be
low oil level for about 2
checked>
hours.
• Check connection and
installation of TK1 and TK2
sensors.
• Check resistance
characteristics of TK1 and
TK2 sensors.
• Check for gas or oil leak in
same line.
• Check for refrigerant
problem inside compressor
casing.
• Check SV3D, SV3F valves
for failure.
• Check oil return circuit of
oil separator for clogging.
• Check oil equalizing circuit
for clogging.