Check code
Outdoor 7-segment display
Controller
Check
Sub-code
code
1∗: Fan P.C.
board 1
2∗: Fan P.C.
board 2
P22
P22
1∗: Compressor
1 side
P25
P25
2∗: Compressor
2 side
1∗: Compressor
1 side
2∗: Compressor
2 side
P26
P26
1∗: Compressor
1 side
2∗: Compressor
P29
P29
2 side
Differs according to
nature of alarm-causing
trouble
P30
(L20 displayed.)
P31
S01
Location
Description
System status
of
detection
Fan INV.
Outdoor fan
All stop
P.C. board
P.C. board
trouble
Compressor
Compressor
All stop
P.C.board
P.C. board
trouble
Compressor
Compressor
All stop
Start up
P.C. board
trouble
Compressor
Compressor
All stop
P.C. board
position
detection circuit
trouble
Central
Group control
Continued
control
follower unit
operation
device
trouble
Duplicated
Continued
central control
operation
address
Indoor unit
Other indoor
Stop of
trouble
corresponding
(group follower
unit
unit trouble)
Central
Central control
Continued
control
device reception
operation
trouble
device
- 221 -
Check code detection
Check items (locations)
condition(s)
Protected operation of Fan
• Check fan motor.
inverter P.C. board
• Check for failure in fan
P.C. board.
• Check connection of fan
motor connector.
• Check power voltage of
the main power supply.
IPM short-circuit is detected
• Check connector
connection and wiring on
compressor P.C.board.
• Check for failure in
compressor P.C.board.
Open phase or IPM
• Check for failure in
overcurrent for compressor
compressor.
is detected.
• Check connection of
connectors/terminals on
compressor and
compressor P.C.board.
• Check winding resistance
between phases of
compressor.
• Check for failure in
compressor P.C.board.
Position detection is not
• Check wiring and
going on normally.
connector connection.
• Check for compressor
layer short-circuit.
• Check for failure in
compressor P.C. board.
Trouble occurs in follower
• Check check code of unit
unit under group control.
that has generated alarm.
([P30] is displayed on central
control remote controller.)
• Check address settings.
There is duplication in
central control addresses.
There is trouble in other
• Check indoor P.C. board.
indoor unit in group,
resulting in detection of
E07/L07/L03/L08.
Central control device is
• Check for failure in central
unable to receive signal.
control device.
• Check for failure in central
control communication line.
• Check terminator resistor
setting.
• Check power supply for
devices at other end of
central control
communication line.
• Check failure in P.C.
boards of devices at other
end of central control
communication line.