How to setup the CODE No. [FE] (Flow Selector unit address)
• As for every single port type FS unit, multi port type FS unit setup CODE No. "FE" within the range of 1~128.
This CODE No. cannot be duplicate in one system.
1. Press and hold "
MENU" button and [∨] setting button simultaneously for 4 seconds or more.
2. Select the "DN setting" using the [∨] and [∧] button and press the "F2(Set)" button.
Select the corresponding "Indoor unit" using the "F1(Unit)" button and push the "F2(Set)"
button.(The fan and louvers of the selected indoor unit will be activated.)
3. Set the Indoor Unit Function Code (I.DN) to [FE] and the data using the [∨] and [∧] button
(The fan of the selected indoor unit is turned on.)
4. When done, press the "
5. Press the "
CANCEL" button and complete the setting for the time being.
1,4
5
How to set up the CODE No. [105] (Flow Selector unit port address)
• As for multi port type FS unit, set up CODE No. "105" within the range of 1~12.
This CODE No. should not be duplicate in one system.
• As for both single port type FS unit set up CODE No. "105" to 1.
1. Press and hold "
2. Select the "DN setting" using the [∨] and [∧] button and press the "F2(Set)" button. Select the
corresponding "Indoor unit" using the "F1(Unit)" button and push the "F2(Set)" button.(The fan and louvers
of the selected indoor unit will be activated.)
3. Set the Indoor Unit Function Code (I.DN) to [105] and the data using the [∨] and [∧] button (The fan of the
selected indoor unit is turned on.)
4. When done, press the "
5. Press the "
CANCEL" button and complete the setting for the time being.
How to set up the CODE No. [106] (Combining branches mode of Flow Selector unit)
• When connecting the indoor units to combining branches of the multi port type FS unit, set up CODE No.
"106" to 1.
• When connecting the indoor units to NOT combining branches of the multi port type FS unit, set up CODE
No. "106" to 0.
1. Press and hold "
2. Select the "DN setting" using the [∨] and [∧] button and press the "F2(Set)" button. Select the
corresponding "Indoor unit" using the "F1(Unit)" button and push the "F2(Set)" button.(The fan and louvers
of the selected indoor unit will be activated.)
3. Set the Indoor Unit Function Code (I.DN) to [106] and the data using the [∨] and [∧] button (The fan of the
selected indoor unit is turned on.)
4. When done, press the "
5. Press the "
CANCEL" button and complete the setting for the time being.
MENU" button.