3 - Ekip Com Profibus DP

Models Two different modules compatible with the Profibus protocol are available: Ekip Com Profibus DP and
Connections The module must be assembled in the first vacant slot of the terminal box after Ekip Supply , either on the
Power supply Ekip Com Profibus DP is supplied directly by the Ekip Supply module to which it is connected.
Interface the module has three signaling leds:
216 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Ekip Com Profibus DP is a communication accessory which allows Ekip Touch to be integrated into an RS-
485 network with Profibus communication protocol, with remote supervision and monitoring functions.
The module is configured as a Slave and remotely, you can:
• read Ekip Touch measurements and information
• manage certain controls, including opening and closing the actuator (MOE-E)
• access information not available on the display
• If connected to a withdrawable version of the circuit-breaker, the allows the racked-in/racked-out
status to be detected
NOTE: the remote open and close commands of the circuit-breaker can only be executed if
Ekip Touch is in the Remote configuration and the circuit-breaker is equipped with the Ekip
Com Actuator module (page 258 )
Ekip Com Profibus DP is always supplied with contacts Ekip AUP and Ekip RTC (page 258).
The System Interface document is available for mapping the module in its communication network. All the
required communication and command details are listed in the document (page 179).
Ekip Com Profibus DP Redundant .
The modules are identical in terms of characteristics and installation methods, except for: display menus,
cabling and addresses for system communication, which are specific for each module.
NOTE: if different indications are not given, the information in the next chapter is valid for
both models
The two modules can be connected at the same time to Ekip Touch so as to expand the potential of the
unit (e.g. for applications where high grid reliability is required).
IMPORTANT: each Ekip Touch can be fitted with only one module per type. The configuration
with two modules of the same model is not allowed (example: two Ekip Com Profibus DP
Redundant)
circuit-breaker (fixed version) or on the fixed part (withdrawable version).
For references about the connection and terminals, please consult document 1SDM000091r0001; use
Belden 3079A type cables or equivalent for the external cabling.
To connect the module to Ekip Touch, please consult document 1SDH001000r0512.
NOTE: communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply