ABB SACE Emax 2 Series Operating Instructions Manual page 293

Low voltage air circuit-breaker
Table of Contents

Advertisement

Programming errors If during the programming of the parameters an attempt is made to violate certain limitations, the trip
290 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
unit blocks the saving procedure and signals the error:
Type of error
2I Th > 15 kA
30006
30007
30008
30011
30012
30013
Active Power Fail
DLog not stopped
D Th ≥ I Th
Zone Sel Config = On while S /
S2 / I / G / Gext / MDGF = On
G Th > 1200 A
G Startup Th > 1200 A
In MDGF > CB Nominal Current
G FT time = 50 ms is not valid
G Time> 400 ms
Gext Time> 400 ms
Gext FT time = 50 ms isn't valid Trip time I41 (protection G) = 50 ms
High priority alarm
I and MCR enabled together
L Th ≥ S Th
L Th ≥ S2 Th
L curve different to I
t=k
2
L Th > 980 A
Neutral configuration error
OV Threshold > 828 V
OV2 Threshold > 828 V
RC toroid error
RQ Q24 ≥ Q25
S Th ≥ I Th
S2 Th ≥ I Th
S Time > 400 ms
S2 Time> 400 ms
S(V) or S2(V) parameters
SYNCHRO parameters error
V DIR Th > 690*1.2
VS Th > 690*1.2
Error description
Threshold I31 (protection 2I) > 15 kA
Parameter change not completed on display within five minutes
Attempt at remote control with Trip unit configuration in the
local mode
Attempt at local control with Trip unit configuration in the
remote mode
Error in Ekip Link list of actors
More than one Time Sync source (IEEE 1588 or SNTP) on one
single module or between different modules
Network Analyzer parameter control unsuccessful
Threshold P23 (protection UP) ≥ Threshold P26 (protection OP)
Modification of datalogger parameters not allowed with
datalogger function not stopped
Threshold I7 (protection D) ≥ Threshold I3 (protection I)
Zone selectivity enabling of protection D not allowed with zone
selectivity already active for one among protections S, S2, I, G,
Gext or MDGF
Threshold I4 (protetion G) > 1200 A with CB in standard
configuration UL
Threshold I4 (protection G) or Threshold I41 (protection Gext or
MDGF) > 1200 A with CB in standard configuration UL
G > 1200 A protection threshold start up with CB in standard
configuration UL
G or Gext or MDGF > 1200 A protection threshold start up with CB
in standard configuration UL
Set size of sensor MDGF exceeds lu size of circuit-breaker
Trip time I4 (protection G) = 50 ms
Trip time t4 (protetion G) > 400 ms with CB in standard
configuration UL
Trip time t41 (protetion Gext or MDGF) > 400 ms with CB in
standard configuration UL
Modification of parameters not allowed during protection times
Protections I and MCR are mutually exclusive
Threshold I1 (protection L) ≥ Threshold I2 (protection S)
Threshold I1 (protection L) ≥ Threshold I5 (protection S2)
Protection curve L different from t=k/I
configuration UL
Threshold I1 (protetion I) > 980 A with CB in standard
configuration UL
Configuration of neutral protection must conform to formula: I1
(A) ≥ Iu (A) x Ne config / 100
Threshold U9 (Protection OV) > 828 V (690 x1.2)
Threshold U16 (Protection OV2) > 828 V (690 x1.2)
Activation of toroid Rc is not allowed without the presence of a
model Rc rating plug
Threshold Q24 ≥ Threshold Q25 (Protection RQ)
Threshold I2 (Protection S) ≥ Threshold I3 (Protection I)
Threshold I5 (Protection S2) ≥ Threshold I3 (Protection I)
Trip time t2 (protetion S) > 400 ms with CB in standard
configuration UL
Trip time t5 (protetion S2) > 400 ms with CB in standard
configuration UL
Error in configuration of parameters of protection S (V) or S2 (V);
consult user manual of Trip unit for the limits
Inconsistency of Synchrocheck protection parameters: Delta
phase ≥ 180 x Delta freq x [minimum correspondence time +
0.0023]
Protection threshold VDIR > 828 V (690 x1.2)
One of the two thresholds of protection VS Warning > 828 V (690 x1.2)
ABB | SACE Emax 2
2
with CB in standard
Alarms or failures