ABB SACE Emax 2 Series Operating Instructions Manual page 231

Low voltage air circuit-breaker
Table of Contents

Advertisement

Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
Remote information Certain integrative information concerning the version and state of the module is available via service
228 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
communication:
Parameter
Description
Defines Dataset (acyclic data) access mode
• each individual acyclic register can be accessed in the Legacy
mode using the Slot, Subslot and Index fields (with Slot fixed at
Data access
3)
mode
• only complete blocks can be accessed in the Dataset mode; Slot
is fixed at 0, Subslot at 1 and Index defines the block reference
See System Interface for details.
Cyclic data
Establishes whether the register of the cyclic data item is
endianess
configured in Big endian or Little endian.
Acyclic data
Establishes whether the register of the acyclic data item is
endianess
configured in Big endian or Little endian.
connector (via Ekip Connect) or through communication via system bus, i.e.,HW and Boot version, CRC
state (correctness of SW in module), DCP Name, network settings (IP address, Network Mask, Gateway
address)
ABB | SACE Emax 2
Default
Legacy
Little endian
Big endian
External electronic accessories
6 - Ekip Com Profinet