ABB SACE Emax 2 Series Operating Instructions Manual page 245

Low voltage air circuit-breaker
Table of Contents

Advertisement

Information in menu The following information will be available in the About - Modules menu if Ekip Touch has detected the
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
242 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
The Remote FW update submenu enables the Firmware update function of the module to be managed;
the following parameters are available:
Parameter
Description
Enables firmware update function of module to be remotely
Enable
activated/deactivated
The parameter is available when Enable = On and allows the
automatic update mode to be activated (On): in the presence
of new Firmware, this latter is updated automatically. If the
Automatic
parameter is Off, updating must be performed in the Manual
mode: in the presence of new Firmware, the message Ekip
Com Hub FW Update appears in the status bar and updating is
performed via the Manual command.
This parameter is available when Enable= On, with Automatic=
Start FW
Off configuration and when new Firmware is present (see
update
description above); allows the Firmware update of the module to
run
module correctly:
Information
Description
SN and version
Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the time
of connection to the network in the case of configuration with a dynamic IP, or
IP address
can be set via the menu in the event of a static IP
NOTE: without a DHCP server, the module automatically adopts a random
IP address within the 169.254.xxx.xxx range
Subnet mask; identifies the method for recognizing the subnet to which the
Network Mask
modules belong and enables modules to be searched for within a defined set
of recipients.
IP address of the node to which the module is connected, in the presence of
Gateway address
several subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal
MAC address
to ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
communication:
Parameter
Description
Allows the CRL (Certificate Revocation List) to be used to
CRL Enable
ascertain whether the server certificate is valid
Clock update
Enables control of the time reference transmitted by the SNTP
hardening
server
enable
SNTP Server
Enables the position of the SNTP server to be set in relation to
Location
the network in which the module is installed
SNTP Time
Defines the time zone to be used for synchronism
zone
SNTP Daylight
Used to select whether daylight saving time is present (ON) or
Saving Time
not (OFF) in the country to which the synchronization time refers
Permits (Enabled ARP) the periodic generation of a Gratuitous
Disable
ARP message, used by Ekip Connect to rapidly find the modules
Gratuitous ARP
via Ethernet scan without knowing the IP address beforehand
Cloud data
Enables/disables the function that collects and transmits the
send enable
module data
JSON data
Allows the compressed format of the JSON file sent to Cloud to
compression
be selected (enable)
ABB | SACE Emax 2
Default
OFF
OFF (manual)
Default
+00:00
OFF
ARP Enabled
OFF
Disabled
External electronic accessories
10 - Ekip Com Hub