Events Ekip Touch can record the last 200 events, mainly concerning variations in the status and operation of the
Tripping Ekip Touch is able to record the last 30 TRIPs.
114 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
unit; in particular:
• configuration status of the bus, operating mode, active set, auxiliary supply
• connection statuses or alarms: current sensors, Trip Coil
• connection statuses or alarms: current sensors, Rating Plug , Trip unit , Trip Coil
• protections: delay in action or alarm
• trip: status of open command, signaling of trips due to protection
NOTE: the first event available in the list is the most recent one; having reached the 200-events
threshold, the oldest events will be progressively overwritten
NOTE: if a numerical alarm is displayed (e.g.: 30002), consult the Events page of the System
Interface to identify the error. Contact ABB if the code is not included in the list.
The complete list is available in the Measurements - Historicals - Events menu, where a set of information
is given for each event: icon of the type of event, name of event, date and time recorded.
There are 4 icons that identify the type of event:
Icon
Description
Event reported for information purposes
Timing of a protection in progress, trip expected
Alarm referring to a non-dangerous condition
Alarm concerning operation, a fault or connection failure
The complete list is available in the Measurements - Historicals - Trips menu, where useful information is
given for each TRIP:
• the protection that caused the trip
• the consecutive number of the trip
• the date and time of the trip (with reference to the internal clock)
• the measurements associated with the tripped protection
NOTE: once the 30-TRIP threshold has been exceeded, the oldest trips are progressively
overwritten
Correlated measurements
The type of protection involved determines the measurements recorded at the moment of tripping:
Protection
Measurements recorded
Current
L1, L2, L3, Ne, Ig Currents
Temperature
L1, L2, L3, Ne Currents
Access to most recent trips
Besides being available in the Historicals menu, information about the most recent trips can be accessed
in three different ways, depending on the conditions of Ekip Touch:
Condition
Trips that have just occurred
with Ekip Touch on
Trips that have just occurred
with Ekip Touch off
Rapid consultation in all the
other conditions
Notes
Ne is available with CBs type 4P and 3P + N; Ig is
available in the case of trips due to G protection
The temperature cannot be displayed
Access
The main page is temporarily replaced by a trip information page;
press the iTEST button to reset and go back to the normal screen
page
Press the iTEST button to display the trip information page for a
few seconds
Press the iTEST button four times from any page other than a
menu, or a page accessed via a menu
ABB | SACE Emax 2
Ekip Touch - Measurements
1 - Standard Measurements