Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
235 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
(1)
communication:
Parameter
Description
Preferred
If several configuration files are present, allows file hierarchy
configuration file
between .cid and .iid to be defined
Allows the IEEE 1588 protocol for distribution of the clock and
Enable IEEE 1558
synchronization signal to be enabled
Enables the module to be set up as a master in the the network
IEEE 1558 Master
segment to which it belongs (synchronization clock).
IEEE 1558 Delay
Allows the data exchange mode between module and master,
mechanism
either Peer-to-Peer or End-to-End, to be selected.
Time zone
Defines the time zone to be used for synchronism
Daylight Saving Time Used to select whether daylight saving time is present (ON) or
not (OFF) in the country to which the synchronization time refers OFF
Defines the file loading procedure:
• TFTP always On = port open, loading always possible
• TFTP enable required = port normally closed. To start loading,
TFTP Security level
Enable TFTP must be run at the start of the procedure and
Disable TFTP must be run at the end of the procedure (disable
not necessary, security command).
Defines the limitations to remote opening and closing command
execution:
• Standard commands = standard commands (unrestricted)
CB Open/CB Close
activated
command
• CB operate request = standard commands not activated. Use
programmable functions YC COMMAND and YO COMMAND,
and Request breaker open (28) and Request breaker close (29)
commands
Analysis of selectivity input from IEC 61850 module can be
Zone Selectivity
enabled/disabled for each of protections S, S2, G, Gext, D, D(BW),
Analysis
D(FW)
Parameter useful if an IEEE 1588 GrandMaster clock is not
available:
• If enabled (ON), the module is seen as an IEEE1588 master
IEEE 1588 Boundary
clock by all the slaves/devices in the same local network, even
clock
when the source of external synchronism is different from IEEE
1588 (SNTP for example)
• If disabled (OFF) the module benefits from the synchronism of
the master in its own network
Enables the Rate limiter function, which limits the number of
Enable package
packages entering the module from the network, to be activated/
Limitation
deactivated
(1)
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
communication:
Information
HW and Boot version
Flash CRC status and result
Ekip Link status
SNTP Server Error
SNTP Server Synchronization
IEEE 1558 status
GOOSE Missing
Configure Mismatch
Decode Error
Sequence number error
Remote programmable statuses (from E to R)
Zone selectivity remote inputs
.
(1)
Description
General module information
Information about the correctness of the SW in
the module
Signals Ethernet cable connection errors
Error in communication with SNTP server
State of synchronism with SNTP server
Valid with Master IEEE 1588= ON, notifies the
presence (Slave or PTP Master Active) or absence
(PTP Master but Passive) of a higher level master
Signals that an expected GOOSE has not been
received
A GOOSE received does not conform to the
expected structure
Condition (true/false) of the programmable states and
information on selectivity arising from logic defined in the
configuration files loaded in module IEC 61850
External electronic accessories
8 - Ekip Com IEC 61850
ABB | SACE Emax 2
Default
.cid
OFF
OFF
End-to-
End
+00:00
TFTP
always
On
Standard
commands
Disabled
(all)
OFF
Disable