ABB SACE Emax 2 Series Operating Instructions Manual page 149

Low voltage air circuit-breaker
Table of Contents

Advertisement

VS Warning A warning signal is activated if all three of the line-to-line voltages measured by the Trip unit are within the
FS Warning A warning signal is activated if the frequency measured by the Trip unit is within the window defined by
F W1 Warning The F W1 Warning function activates the alarm (without commanding TRIP) if the frequency measured by
146 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
window defined by the control thresholds for the set time.
The Protections-Advanced-Warnings menu includes the control threshold submenu in which the
parameters can be entered:
Parameter
Description
Activates/deactivates monitoring of the parameters and their
Enable
availability in the menu
Defines whether the line-to-line voltages to be verified are those from
the internal sockets ( Measurement module) or from Ekip Synchrocheck ,
if present.
Signal source
NOTE: if Ekip Synchrocheck is set, monitoring will refer to one
single voltage
Establishes the lower value of the control band, given as both absolute
Threshold
value (V) and relative value (Un), which can be set within the range: 0.5
DOWN
Un to 1 Un in 0.001 Un steps
Establishes the upper value of the control band, given as both absolute
Threshold UP
value (V) and relative value (Un), which can be set within the range: 1 Un
to 1.5 Un in 0.001 Un steps
This is the monitoring time that activates the signal; the value is given
Time
in seconds and can be set within a range: 0.1 s to 900 s, in 0.1 s steps
the control thresholds for the set time.
The Protections-Advanced-Warnings menu includes the control threshold submenu in which the
parameters can be entered:
Parameter
Description
Activates/deactivates monitoring of the parameters and their
Enable
availability in the menu
Defines whether the frequencies of the line-to-line voltages to be
verified are those from the internal sockets ( Measurement module) or
Ekip Synchrocheck , if present.
Signal source
NOTE: if Ekip Synchrocheck is set, monitoring will refer to one
single voltage
Establishes the lower limit value of the control band, given as both
Threshold
absolute value (Hertz) and relative value (Fn), which can be set within
DOWN
the range: 0.9 Fn to 1 Fn in 0.001 Fn steps
Establishes the lower limit value of the control band, given as both
Threshold UP
absolute value (Hertz) and relative value (Fn), which can be set within
the range: 1 Fn to 1.1 Fn in 0.001 Fn steps
This is the monitoring time that activates the signal; the value is given
Time
in seconds and can be set within the range: 0.1 s to 900 s, in 0.1 s steps
Ekip Touch exceeds or drops below the set threshold value (depending on the direction set).
The Protections-Advanced menu includes the F W1 Warning submenu via which the following parameters
can be configured:
Parameter
Description
Activates/deactivates the control threshold of the parameters and their
Enable
availability in the menu
Defines whether frequency monitoring is performed after the
Direction
measured sequence has dropped (Down) or been exceeded (Up)
Establishes the value that activates the alarm.
Threshold
The value is given as both absolute value (Hertz) and relative value (Fn)
and can be set within the range: 0.9 Fn to 1.1 Fn in 0.001 Fn steps
ABB | SACE Emax 2
Default
Off
Meas.
0,9 Un
1,1 Un
30 s
Default
Off
Meas.
0,998 Fn
1,002 Fn
30 s
Default
Off
Down
3 Fn
Ekip Touch - Additional functions
5 - IPS Interface protections