S33 M/2: springs charged
signalling contact
203 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
The S33 M/2 contact signals the state of the closing springs of the circuit-breaker control (charged or
discharged).
It is available in two types:
• standard contact
• contact for digital signals
NOTE: the S33_M/2 contact is always included in the gearmotor for automatic charging of
the springs in the standard version. The version for digital signals must be requested with
the order for the motor.
35
36
38
S33
S33 M/2 for E1.2
35
36
38
S33
S33 M/2 for E2.2 - E4.2 - E6.2
The following table provides information on the electrical characteristics:
Characteristics
24V
DC
125V
250V
Breaking
250V
capacity
AC
400V
Minimum load
S33/M2: Connections
More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
includes the entire circuit diagram 1SDM000091r0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/
DownloadCenter/, in particular for E1.2 in the kit sheet
kit sheet 1SDH001000r0609.
Standard
-
0.5A @ 0ms / 0.3A @ 10ms
0.3A @ 0ms / 0.15A @ 10ms
3A cosφ 0,3
5A cosφ 0,7
5A cosφ 1
3A cosφ 1
2A cosφ 0,7
1A cosφ 0,3
100mA @ 24V
1SDH000999r0609
2 - Electrical signalling accessories
ABB | SACE Emax 2
Digital signals
0.1 A
-
-
-
-
-
-
-
-
1mA @ 5V
and for E2.2-E4.2-E6.2 in the