Inverter and peripheral devices
1.2.1

Peripheral devices

Check the inverter model of the inverter you purchased. Appropriate peripheral devices must be selected according to
the capacity. Refer to the following list and prepare appropriate peripheral devices:
200V class
Motor Output
Applicable Inverter Model
(kW(HP))
0.4 (1/2)
FR-A720-00030-NA/N4
0.75 (1)
FR-A720-00050-NA/N4
1.5 (2)
FR-A720-00080-NA/N4
2.2 (3)
FR-A720-00110-NA/N4
3.7 (5)
FR-A720-00175-NA/N4
5.5 (7.5)
FR-A720-00240-NA/N4
7.5 (10)
FR-A720-00330-NA/N4
11 (15)
FR-A720-00460-NA
15 (20)
FR-A720-00610-NA
18.5 (25)
FR-A720-00760-NA
22 (30)
FR-A720-00900-NA
30 (40)
FR-A720-01150-NA
37 (50)
FR-A720-01450-NA
45 (60)
FR-A720-01750-NA
55 (75)
FR-A720-02150-NA
75 (100)
FR-A720-02880-NA
90 (125)
FR-A720-03460-NA
*1
Select the MCCB according to the power supply capacity. Install one MCCB per inverter.
For installation in the United States, Class RK5, Class J, Class CC, Class L, Class T or any faster acting fuses
or UL 489 Molded Case Circuit Breaker (MCCB) must be provided, in accordance with the National Electrical
Code and any applicable local codes.
For installation in Canada, Class RK5, Class J, Class CC, Class L, Class T or any faster acting fuses or UL
489 Molded Case Circuit Breaker (MCCB) must be provided, in accordance with the Canada Electrical Code
and any applicable provincial codes. (Refer to
*2
Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC
with class AC-3 rated current for the motor rated current.
CAUTION
 When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model and cable and reactor according to the motor output.
 When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the
inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.
REMARKS
 Motor Output (kW) in the above table indicates values when using the Mitsubishi 4-pole standard motor with power supply
voltage of 200VAC 50Hz.
4
Moulded Case Circuit Breaker
(MCCB)
or Earth Leakage
*1
Circuit Breaker (ELB)
Power factor improving
(AC or DC) reactor
without
5A
5A
10A
10A
15A
15A
20A
15A
30A
30A
50A
40A
60A
50A
75A
75A
125A
100A
150A
125A
175A
150A
225A
175A
250A
225A
300A
300A
400A
350A
400A
400A
Installation Guideline.)
Input Side Magnetic Contactor
Power factor improving
(AC or DC) reactor
with
without
S-N10
S-N10
S-N10
S-N10
S-N20, S-N21
S-N25
S-N25
S-N35
S-N50
S-N65
S-N80
S-N95
S-N150
S-N180
S-N220
*2
with
S-N10
S-N10
S-N10
S-N10
S-N10
S-N20, S-N21
S-N25
S-N35
S-N50
S-N50
S-N65
S-N80
S-N125
S-N150
S-N180
S-N300
S-N300
MCCB
INV
IM
MCCB
INV
IM