2.3 Wiring to the Connector

2.3 Wiring to the Connector

2.3.1 Suitable Parts and Tools

A spring connection type is used for the terminal block of the analog I/O section. Perform wire
connection properly by referring to the compatible products listed in the following tables.
Compatible wires (stranded wire)
Size
AWG24 to AWG16
Rod terminals with compatible insulation sleeve
Manufacturer
Phoenix Contact Co., Ltd.
Crimping tool dedicated to rod terminals
Manufacturer
Phoenix Contact Co., Ltd.

2.3.2 Wire Connection Method

Perform wire connection of the terminal block according to the following procedure.
1.
Strip the sheath from the electric wire.
10 mm
2.
While pressing the tab on the terminal block using a flat-blade screwdriver, insert the wire
all the way until it stops. Confirm that the electric wire is fixed in place when the screwdriver
is released.
2-8
Nominal cross-sectional area
0.2 mm
Cross-sectional
Size
area
AWG24
2
0.25 mm
AWG20
2
0.50 mm
AWG18
2
0.75 mm
AWG18
2
1.00 mm
Model number
CRIMPFOX UD 6
2
2
to 1.5 mm
Model number
AI 0,25-6 YE
AI 0,5-6 WH
AI 0,75-6 GY
AI 1-6 RD
Product No.
1204436
WUME-FPXHAIO-01