3.4.2 Analog Input Range Setting

When a set value is entered in the "Input range setting area" using the user program, the
analog input range is set in the unit
● When H1 to H7 is entered in the "Input range setting area", the analog input is started.
● If a change is made to the program after the mode is changed to the PROG. mode, cycle the
power.
Sample program
If an expansion is made to the 1st unit, set as follows using the user program to set the 0 to +10
V range to CH0 and CH1 and the 0 to +5 V range to CH2 and CH3.
R0
Input range setting
H1: 0 to +10 V
H2: 0 to +5 V
H3: 0 to +20 mA
H4: -10 to +10 V
H5: -5 to +5 V
H6: +1 to +5 V
H7: +4 to +20 mA
H0, H8 to F: Do not use the analog input.
WUME-FPXHAIO-01
No. of averaging times
F0 MV
3.4 Analog Input Functions
Specifications
Set to 64 times / 128 times
Disconnection detection is possible when set to +1 to
+5 V and +4 to +20 mA ranges
(Detection level: 0.7 V or less, 2.8 mA or less)
H2211
WY30
3-13