Averaging Processing Setting 1 - Panasonic AFPXHEAD4 User Manual

Programmable controller fp-xh expansion analog unit
Table of Contents

Advertisement

3.3 Stored Data of the Output Contact (WY)
3.3.3 Averaging Processing Setting
When an averaging processing setting is entered, the analog average count is set.
Applicable model
Model
AFPXHEAD4
AFPXHEAD8
AFPXHEA21
Averaging processing setting
H1: Moving average 10 times (Maximum and minimum values are deleted.)
H2: No. of averaging times: 64 times
H3: No. of averaging times: 128 times
H0, H4 to F: Do not use the averaging processing.
I/O allocation
Channel
Averaging
processing setting 1
CH0 to CH3
Averaging
processing setting 2
CH4 to CH7
I/O contents

Averaging processing setting 1

The range setting data for each channel data is allocated from the lower level in the order of
CH0, CH1, CH2, and CH3.
Averaging processing setting 2
The range setting data for each channel data is allocated from the lower level in the order of
CH4, CH5, CH6, and CH7.
3-10
Expansion location
1st unit
2nd unit
3rd unit
WY32
WY42
WY52
WY33
WY43
WY53
Channel
CH0 to CH3
CH0 to CH7
CH0 to CH1
4th unit
5th unit
6th unit
WY62
WY72
WY82
WY63
WY73
WY83
7th unit
8th unit
WY92
WY102
WY93
WY103
WUME-FPXHAIO-01

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afpxhead8Afpxheda4Afpxhea21