12.3.26 BakTrpImp

Backup trip impulse relay; closes immediately if any of the
65)
is activated and CB Feedback doesn't deactivate within Bak Trp Del. The length of the impulse can be
adjusted in
Imp Len [s] (page
terminated in fault free state after a successful fault reset. During trip status, the relay does not react on any
new failure and also, if the CB Feedback input or Bak Trp output are not configured on any physical input or
output, this function is blocked.
6 back to Relay outputs

12.3.27 !BakTrpImp

Inverse backup trip impulse relay; opens immediately if any of the
(page 65)
is activated and CB Feedback doesn't deactivate within Bak Trp Del. The length of the impulse can
be adjusted in
Imp Len [s] (page
terminated in fault free state after a successful fault reset. During trip status, the relay does not react on any
new failure and also, if the CB Feedback input or Bak Trp output are not configured on any physical input or
output, this function is blocked.
6 back to Relay outputs

6 back to Appendix

MainsPro G99TT 1.0.0 Global Guide
55). Opening of the relay does not mean end of trip state. The trip is
55). Closing of the relay does not mean end of trip state. The trip is
CommTrpPer (page 65)
CommTrpPer (page 65)
or
CommTrpImp (page
or
CommTrpImp
70