Group: V <>, A; V>, V>>, V<, V<<, A.v>, A.v>>, A.v<, A.v<< [V]; V> Del, V>> Del, V< Del, V<< Del [S]; Avg V> [V] - ComAp MainsPro G99TT Global Manual

Mains decoupling protection relay
Table of Contents

Advertisement

12.1.2 Group: V <>, A.V <>
V>, V>>, V<, V<<, A.V>, A.V>>, A.V<, A.V<< [V]
Threshold of 1st and 2nd stage overvoltage, and 1st and 2nd stage undervoltage protection, respectively.
Range
1..999 V
0
= OFF, the appropriate stage of voltage protection is not enabled
Default setting
Note: Please note, that the indicated setting is adjusted for "Star" connection of the measured voltage, i.e.
ph-to-N voltage measurement. In case of using "Delta" connection, the appropriate change of the setpoints to
ph-ph voltage is necessary.
6 back to Library of Setpoints
V> del, V>> del, V< del, V<< del [s]
Delay of the appropriate stage of the voltage protection.
Range
0.00..600.00 s
Default setting
6 back to Library of Setpoints
Avg V> [V]
Limit for
Floating 10 minutes average overvoltage (page 34)
Range
0..34000 V
0
= OFF, the 10 minutes average overvoltage protection is not enabled
Default setting
0 (OFF)
6 back to Library of Setpoints
MainsPro G99TT 1.0.0 Global Guide
V>
262 V
V>>
273 V
V<
184 V
V<<
0 V
V> Del
1.00 s
V>> Del
0.50 s
V< Del
2.50 s
V<< Del
0.50 s
protection.