7.2 Fault reset

Fault reset is an event, caused by one of the following reasons:
FltRes button is pressed
Binary switch Fault reset is activated
Automatic fault reset timer set by setpoint
started in the moment when all evaluated values are back within their limits. If during the count-down
another fault status appears, the timer is reset and started only after all evaluated values are back within
their limits again.
The above mentioned reasons are a trigger to perform Fault reset. The actual Fault reset is performed only in
case the TRIP status is active and all evaluated values have returned back into limits.
The Fault reset will not be performed if the following is true:
The TRIP is not active
The TRIP is active but any of the measured values is out of limits of normal operational state
In such cases the Fault reset trigger is ignored.
By a successful Fault reset, the TRIP status is terminated.
6 back to TRIP and Fault Reset
MainsPro G99TT 1.0.0 Global Guide
Auto FR Del [s] (page 55)
has counted down. The timer is