4.5 Alarm messages

One of these indications appears on the homepage screen in case of the unit trip. It indicates the first
protective stage, which issued the trip event:
f>
f>>
f<
MainsPro G99TT 1.0.0 Global Guide
Overfrequency, 1st stage
Overfrequency, 2nd stage
Underfrequency, 1st stage
Last Trip: indication of the latest event,
which caused trip. See the following
chapter for trip messages explanation.
TripCnt: total counter of MainsPro
G99TT trips since the MainsPro G99TT
unit counters reset
U: counter of overvoltage and
undervoltage -related trips
f: counter of overfrequency and
underfrequency - related trips
LOM: counter of Loss-of-Mains -
related trips (Vector shift and ROCOF)
Otr: counter of trips with other reason
than the above mentioned: Ext1 or Ext2
trip, voltage asymmetry, phase
sequence or inverse phase polarity
Operation Time: time since MainsPro
G99TT was powered up*
Last Trip Time: time of the latest trip
since MainsPro G99TT was powered-
up
Please note that the time information on
the MainsPro G99TT unit is not measured
by a calibrated RTC device and may serve
for orientation purposes only. Find more in
Technical data (page
45).
List of last five trips - contains reason of the
trip and time since the unit was powered up
27