Group: Lom, A.lom; Rstf>,F>> [%F>]; Vs Lim, A.vs Lim [°]; Rocof, A.rocof [Hz/S] - ComAp MainsPro G99TT Global Manual

Mains decoupling protection relay
Table of Contents

Advertisement

Rstf>,f>> [%f>]
Frequency level at which the protection activates again after a trip caused by overfrequency. The TRIP status
will be terminated.
Range
90.0 - 100.0 %f>
0
= OFF, the reset threshold is not activated
Default setting
100.0 %f>
6 back to Library of Setpoints
Rstf<,f<< [%f<]
Frequency level at which the protection activates again after a trip caused by underfrequency. The TRIP
status will be terminated.
Range
100.0 - 110.0 %f<
0
= OFF, the reset threshold is not activated
Default setting
100.0 %f<
6 back to Library of Setpoints

12.1.5 Group: LOM, A.LOM

VS lim, A.VS lim [°]
Threshold at which the Vector shift protection is activated.
Range
1..50°
0
= OFF, the Vector shift protection is not enabled
Default setting
6 back to Library of Setpoints

ROCOF, A.ROCOF [Hz/s]

Threshold at which the Rate of change of frequency (ROCOF) protection is activated.
Range
0.01..10.00 Hz/s
0
= OFF, the ROCOF protection is not enabled
Default setting
1
6 back to Library of Setpoints