Ext; F.r; Alt; Disable - ComAp MainsPro G99TT Global Manual

Mains decoupling protection relay
Table of Contents

Advertisement

Ext

Enables or disables the functionality of the External trip.
external trip is enabled and binary input with
ENABLED
function can be used to induce external trip
DISABLED
external trip is disabled
Default setting
ENABLED
6 back to Library of Setpoints

F.R.

Enables or disables the functionality of the Fault reset binary switch and the button Fault reset.
ENABLED
the binary switch and the button is enabled for fault reset
DISABLED
the binary switch and the button is disabled for fault reset
Default setting
DISABLED
6 back to Library of Setpoints

Alt

Enables or disables the functionality of the Alternative settings binary switch.
ENABLED
the binary switch is enabled
DISABLED
the binary switch is disabled
Default setting
ENABLED
6 back to Library of Setpoints

Disable

Enables or disables the functionality of the Disable binary switch.
ENABLED
the binary switch is enabled
the binary switch is enabled only in case the unit is not in TRIP state. If the fault was
ENABLEDexlTRP
not reset after its detection, activation of the BI Disable will have no influence on the
unit operation until fault reset is performed
DISABLED
the binary switch is disabled
Default setting
DISABLED
6 back to Library of Setpoints
MainsPro G99TT 1.0.0 Global Guide
Ext1 (page 63)
or
Ext2 (page 63)
56