Phase Rotation, Incorrect Phase Polarity - ComAp MainsPro G99TT Global Manual

Mains decoupling protection relay
Table of Contents

Advertisement

Note: ROCOF is sensitive to voltage jumps, therefore it is recommended to be disabled during tests of
overvoltage and enabled after tests are finished.

8.7 Phase rotation, incorrect phase polarity

MainsPro G99TT provides check of the phase sequence and polarity. The correct connection is indicated in
the wiring instructions e.g. on MainsPro G99TT box or in chapter
system is expected on the mains side. It may happen, that e.g. by redesign in the mains or generator site
installation, the phase rotation changes. MainsPro G99TT ensures in such case, that this state is indicated
and it prevents incorrect closing of the circuit breaker by its standard protective functionality. To allow phase
sequence or incorrect phase polarity check, the phase angle between the 3 voltage vectors is expected in
range 120° +/- 30°. If a wrong phase arrangement is detected,
LED signalization is given. The reconnection of measurement terminals is necessary to ensure further proper
functionality of the unit.
6 back to Protective features
MainsPro G99TT 1.0.0 Global Guide
Wiring (page
11), where clockwise rotation
TRIP (page 31)
is issued and the appropriate
39