Group: Basic; Uin; System; Dispt [Min] - ComAp MainsPro G99TT Global Manual

Mains decoupling protection relay
Table of Contents

Advertisement

6 back to Appendix

12.1.1 Group: Basic

Uin

Selection of the measurement range to adjust the HW for maximum accuracy.
230 V
the unit measures 230 VAC phase-neutral with max over-range 130% (300 VAC)
400 V
the unit measures 400 V phase-phase with max over-range 130% (520 VAC)
the unit measures 120 VAC phase-neutral or on the secondary winding of the VT with
120 V
max over-range 130% (156 VAC)
Default setting
230 V
6 back to Library of Setpoints

System

Selection of single phase or three-phase application. In case of single phase setting, the voltage on last two
phases and voltage asymmetry are not measured.
3ph
the unit measures 3-phase system
1ph
the unit measures single-phase system
Default setting
3ph
6 back to Library of Setpoints

DispT [min]

Setting of display backlight timeout since the last button activity.
Range
1..60 min
0 min
= OFF, display is set to permanent backlight
Default setting
0 min
6 back to Library of Setpoints

Auto FR

Enables or disables the functionality of the automatic fault reset by internal timer.
ENABLED
the functionality is enabled
DISABLED
the functionality is disabled
Default setting
ENABLED
6 back to Library of Setpoints
MainsPro G99TT 1.0.0 Global Guide