Commtrpper; Commtrpimp; Commsigimp - ComAp MainsPro G99TT Global Manual

Mains decoupling protection relay
Table of Contents

Advertisement

12.3.1 CommTrpPer

Common trip permanent relay; closes at any failure with a delay given by appropriate parameter. The relay is
kept in open position in a fault-free state and closes immediately in case of LOM protection (Vector shift or
ROCOF), External trip, incorrect phase rotation or wrong phase polarity. Relay opens in fault free state after
successful fault reset. In case of LOM protection, the delay
timed out and after this time it is possible to perform
6 back to Relay outputs

12.3.2 !CommTrpPer

Inverse common trip permanent relay; opens at any failure with a delay given by appropriate parameter. The
relay opens immediately in case of LOM protection (Vector shift or ROCOF), External trip, incorrect phase
rotation or wrong phase polarity. Relay closes in fault free state after a successful fault reset. In case of LOM
protection, the delay
LOM Trp Del, A.LOM Trp Del [s] (page 61)
to perform Fault reset.
6 back to Relay outputs

12.3.3 CommTrpImp

Common trip impulse relay; closes at any failure with a delay given by appropriate parameter. The relay is
kept in open position in a fault-free state and closes immediately in case of LOM protection (Vector shift or
ROCOF), External trip, incorrect phase rotation or wrong phase polarity. Relay opens after
(page 55)
has timed out, his opening however does not mean end of trip state! Trip is terminated in fault free
state after a successful fault reset. In case of LOM protection, the delay
(page 61)
is timed out and after this time it is possible to perform Fault reset. During trip status, the relay does
not react on any new failure.
6 back to Relay outputs

12.3.4 !CommTrpImp

Inverse common trip impulse relay; opens at any failure with a delay given by appropriate parameter. The
relay opens immediately in case of LOM protection (Vector shift or ROCOF), External trip, incorrect phase
rotation or wrong phase polarity. Relay closes after Basic: Imp Len has timed out, his closing however does
not mean end of trip state! Trip is terminated in fault free state after a successful fault reset. In case of LOM
protection, the delay
LOM Trp Del, A.LOM Trp Del [s] (page 61)
to perform Fault reset. During trip status, the relay does not react on any new failure.
6 back to Relay outputs

12.3.5 CommSigImp

Immediate impulse signaling relay; closes immediately at any failure. The relay opens after
(page 55)
since its closing. Any other detected fault-state during run of this timer has no effect. Fault reset
has no influence on this output.
6 back to Relay outputs
MainsPro G99TT 1.0.0 Global Guide
LOM Trp Del, A.LOM Trp Del [s] (page 61)
Fault reset (page
32).
is timed out and after this time it is possible
LOM Trp Del, A.LOM Trp Del [s]
is timed out and after this time it is possible
is
Imp Len [s]
Imp Len [s]
65

Advertisement

Table of Contents
loading