Du Sig; Other Sig; Alt Sig; Trpendimp - ComAp MainsPro G99TT Global Manual

Mains decoupling protection relay
Table of Contents

Advertisement

12.3.16 !dU Sig

Inverse immediate signaling relay – asymmetry; opens immediately in case of voltage (amplitude) unbalance,
positive sequence undervoltage, negative sequence overvoltage, or failure (over or under frequency). The
relay closes in case that all three methods of voltage asymmetry are in fail-free state, but no sooner than after
Imp Len [s] (page 55)
Basic: Imp Len since trip status activation. Fault reset has no influence on this output. If any asymmetry
protection is disabled by setpoint (limit set to 0), the output does not signal activation of this protection stage.
6 back to Relay outputs

12.3.17 Other Sig

Immediate signaling relay – other failures; closes immediately in case of incorrect phase rotation, wrong
polarity of one phase or External trip. The relay opens in case that all observed failures are not active, but no
sooner than after
Imp Len [s] (page 55)
opens no sooner than Basic: Imp Len since trip status activation. Fault reset has no influence on this output.
6 back to Relay outputs

12.3.18 !Other Sig

Inverse immediate signaling relay – other failures; opens immediately in case of incorrect phase rotation,
wrong polarity of one phase or External trip. The relay closes in case that all observed failures are not active,
but no sooner than after
closes no sooner than Basic: Imp Len since trip status activation. Fault reset has no influence on this output.
6 back to Relay outputs

12.3.19 Alt Sig

This output signals activation of binary input Alt Setting.This output is activated as long as alternative setting
is active and Alt setting is enabled.
6 back to Relay outputs

12.3.20 TrpEndImp

Impulse at the end of the TRIP state. The output is normally activated during operation of the unit. The output
deactivates at the end of the
period given by the parameter
In case of subsequent trip in the moment of the output deactivation, the countdown of the Imp Len delay is not
interrupted and the output stays deactivated for the complete Imp Len period. If in that period the TRIP state is
terminated again, the deactivation period is prolonged to Imp Len from the latest Fault Reset. If during TRIP
state the unit is disabled by the input
case of a successful Fault reset.
The output can generally be used for closing the circuit breaker by the ON coil.
6 back to Relay outputs
MainsPro G99TT 1.0.0 Global Guide
from its activation. If the relay is open during trip activation, it closes no sooner than
from its activation. If the relay is closed during trip activation, it
Imp Len [s] (page 55)
from its activation. If the relay is open during trip activation, it
TRIP (page 31)
(i.e. after successful
Imp Len [s] (page
Disable (page
Fault reset (page 32)
55).
63), the output TrpEndImp is deactivated, same as in
is performed) for
68