Trpendimp; Internfail; Baktrpper - ComAp MainsPro G99TT Global Manual

Mains decoupling protection relay
Table of Contents

Advertisement

12.3.21 !TrpEndImp

Inverse impulse at the end of the TRIP state. The output is normally deactivated during operation of the unit.
The output activates at the end of the
performed) for period given by the parameter
In case of subsequent trip in the moment of the output activation, the countdown of the Imp Len delay is not
interrupted and the output stays activated for the complete Imp Len period. If in that period the TRIP state is
terminated again, the activation period is prolonged to Imp Len from the latest
TRIP state the unit is disabled by the input
case of a successful Fault reset.
The output can generally be used for closing the circuit breaker by the ON coil.
6 back to Relay outputs

12.3.22 InternFail

Immediate signaling relay – internal failures; closes immediately in case of internal software failure, including
watchdog activation. The relay opens in case that all observed failures are not active, but no sooner than after
Imp Len [s] (page 55)
Basic: Imp Len time is up. Fault reset, performed either by pressing the Fault reset button or through binary
input, has no influence on this output.
6 back to Relay outputs

12.3.23 !InternFail

Inverse immediate signaling relay – internal failures; opens immediately in case of internal software failure,
including watchdog activation. The relay closes in case that all observed failures are not active, but no sooner
than after
Imp Len [s] (page 55)
sooner than Basic: Imp Len time is up. Fault reset, performed either by pressing the Fault reset button or
through binary input, has no influence on this output.
6 back to Relay outputs

12.3.24 BakTrpPer

Backup trip permanent relay; closes if any of the
activated and CB Feedback doesn't deactivate within Bak Trp Del. Resets by successful fault reset or if the
CB Feedback deactivates before the countdown stops.
If the CB Feedback input or Bak Trp output are not configured on any physical input or output, this function is
blocked.
6 back to Relay outputs

12.3.25 !BakTrpPer

Inverse backup trip permanent relay; opens if any of the
65)
is activated and CB Feedback doesn't deactivate within BakTrpPer (page 1). Resets by successful fault
reset or if the CB Feedback deactivates before the countdown stops.
If the CB Feedback input or Bak Trp output are not configured on any physical input or output, this function is
blocked.
6 back to Relay outputs
MainsPro G99TT 1.0.0 Global Guide
TRIP (page 31)
Imp Len [s] (page
Disable (page
from its activation. If the relay is closed during trip activation, it opens no sooner than
from its activation. If the relay is open during trip activation, it closes no
(i.e. after successful
55).
63), the output TrpEndImp is activated, same as in
CommTrpPer (page 65)
CommTrpPer (page 65)
Fault reset (page 32)
is
Fault reset (page
32). If during
or
CommTrpImp (page 65)
or
CommTrpImp (page
is
69