Device Setup; Partition Number - Digital Monitoring Products 1912XR Programming Manual

Command processor panel
Hide thumbs Also See for 1912XR:
Table of Contents

Advertisement

4.1

DEVICE SETUP

4.2
MAX PARTITION: 1
Changing the number of partitions resets user codes: Whenever you change the number of
partitions on the 1912XR, all programmed user codes are cleared. The only code available after a
partition change is the factory default of 99.
4.3
DEVICE 1: STNDRD
STD
NONE
4.4
PARTITION NO:
Digital Monitoring Products, Inc.
This section allows you to define the physical configuration of the 1912XR panel.
Enter the number of partitions in the system and the types of devices installed at
each address along with their assigned partition. You can install and address up
to eight devices on the keypad data bus.
A description of each option follows:
Maximum number of partitions you want in this system. You can choose from 1 to
4. To change the number displayed, press any SELECT key, enter the number of
partitions you want to enable, and press COMMAND.
Partitions
E n a b l e d
Partition 1
Partitions 1 & 2
Partitions 1 to 3
Partitions 1 to 4
Figure 5: Areas and user codes available with partitioning
Description of the device set to this address. Leave the default STNDRD for 670,
770, and 771 Security Command keypads and for all expander modules.
If the device description does not match the device installed for this address,
press any SELECT key and choose the correct one from those displayed.
STANDARD - The device is either a 670, 770, or 771 keypad, a 711, 714, or 715
Loop Expander, a 6155LX PIR, or a 5845LX Glassbreak.
NONE - No device is set for this address.
Press the SELECT key under the correct device description to change the current
selection. If you entered 2, 3, or 4 in section 4.2 MAX PARTITION, the keypad
displays the following prompt. If there is only one partition programmed in section
4.2, the keypad does not display the partition assignment prompt.
1
Enter the partition number where the current device being programmed is
assigned. For systems with only one partition, leave this entry at one. For
systems with more than one partition, press any top row SELECT key then enter
a 2, 3, or 4. Press COMMAND to program the next device.
Page 11
Areas Available
User Code Numbers
1 to 8
Partition 1 - 1 to 8
Partition 1 - up to 50
Partition 2 - 1 to 4
Partition 2 - up to 50
Partition 1 - 1 to 8
Partition 1 - up to 25
Partition 2 - 1 to 4
Partition 2 - up to 25
Partition 3 - 1 to 4
Partition 3 - up to 25
Partition 1 - 1 to 8
Partition 1 - up to 25
Partition 2 - 1 to 4
Partition 2 - up to 25
Partition 3 - 1 to 4
Partition 3 - up to 25
Partition 4 - 1 to 4
Partition 4 - up to 25
4-DEVICE SETUP
1 to 99
1912XR Programming

Advertisement

Table of Contents
loading