4-Pipe Fan Coil Unit - Siemens RDG20 KN Series Basic Documentation

Room thermostats, communicating and standalone
Hide thumbs Also See for RDG20 KN Series:
Table of Contents

Advertisement

4
Functions
Control sequences

4.7.7 4-pipe fan coil unit

Heating and cooling
4-pipe application with
manual changeover
On/Off control
90 | 186
In 4-pipe applications, the thermostat controls 2 valves in heating and cooling
mode, heating/cooling mode by manual selection. Heating and cooling mode (P001
= 4) is factory-set.
The heating or cooling output can be released via operating mode button if P001 is
set to Manual (P001 = 3).
The diagrams below show the control sequence for On/Off control.
Heating and cooling mode (P001 = 4)
Heating mode with manual selection
(P001 = 3) or
energy saving (P010 = 2 & P014) in
heating sequence
T[°C]
Room temperature
w
Room temperature setpoint
X
Dead zone (P055)
dz
Cooling mode with manual selection
(P001 = 3) or
energy saving (P010 = 2 & P015) in
cooling sequence
YH
Control command "Valve"
(heating)
YC
Control command "Valve"
(cooling)
SDH
Switching differential "Heating"
(P051)
SDC
Switching differential "Cooling"
(P053)
A6V11545892_en--_e