4.4 Application overview
Remote configuration
A6V11545892_en--_e
The RDG2.. room thermostats support the following applications, which can be
configured using the DIP switches at the rear of the unit or commissioning tool.
Set DIP switches 1...5 to OFF (remote configuration, factory setting) to select an
application via commissioning tool.
Remote configuration, via commissioning tool (factory setting)
●
Synco ACS (RDG2..KN)
●
ETS (RDG2..KN)
●
Commissioning via Siemens smartphone application PCT
Go
RDG20..
Application
Fan coil fan speed
ON: 3-speed
OFF: DC 0...10 V
FCU control outputs #1
ON: 3-position
OFF: 2-position
FCU control outputs #2
ON: 3-position
OFF: 2-position
Scheduler
ON: Enable
OFF: Disable
Icon
Description
Heating/cooling
register
Heating register
Chilled/heated
ceiling
Heat
pump/compressor
Application overview
RDG26..
Application
Fan coil fan speed
ON: 3-speed
OFF: DC 0...10 V
Control outputs #1
ON: On/Off
OFF: DC 0...10 V
Control outputs #2
ON: On/Off or 6-port valve DC
invert
OFF: DC 0...10 V or 6-port valve
DC non-invert
Scheduler
ON: Enable
OFF: Disable
Icon
4
Functions
ON =
DIP NO.: 1...5
OFF =
DIP NO.: 1...5
Description
Cooling register
Electric heater
Chilled ceiling
Radiator
43 | 186