2-Pipe Fan Coil Unit - Siemens RDF301 Basic Documentation

Semi-flush mount communicating room thermostats
Hide thumbs Also See for RDF301:
Table of Contents

Advertisement

ON/OFF control
Control sequence
ON/OFF output
Modulating control: 3-position
Control sequence
modulating output
Notes:
Setting the sequence and the control outputs
38 / 94
Siemens
Building Technologies
3.6.3

2-pipe fan coil unit

On 2-pipe applications, the thermostat controls a valve in heating / cooling mode
with changeover (automatically or manually), heating only, or cooling only. Cooling
only is factory-set (P01 = 1).
The diagrams below show the control sequence for 2-position control.
Heating mode
Y
Y1
1
w
0
T[°C]
½ SDH
½ SDH
T[°C] Room temperature
w
Room temperature setpoint
Y1
Control command "Valve" or "Compressor"
The diagrams below show the control sequence for modulating PI control.
Heating mode
Y [%]
Y1
100
0
T[°C]
w
XpH
T[°C]
Room temperature
w
Room temperature setpoint
Y1
Control command "Valve"
∂ The diagrams only show the PI thermostat's proportional part.
∂ For the fan sequence see section 3.8.
Refer to section 3.4, section 3.6.1 and section 3.7.
RDF301, RDF301.50..., RDF600KN, RDF600KN/S
Cooling mode
Y
Y1
1
w
0
½ SDC
½ SDC
SDH
Switching differential "Heating" (P30)
SDC
Switching differential "Cooling" (P31)
Cooling mode
Y [%]
Y1
100
0
w
XpC
XpH
Proportional band "Heating" (P30)
XpC
Proportional band "Cooling" (P31)
Basic Documentation
T[°C]
T[°C]
CE1P3171en
2017-12-07

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rdf301.50hRdf301.50Rdf600kn/sRdf600knRdf301.50 seriesKnx rdf301 ... Show all

Table of Contents