Functions
Additional functions
Note
Humidification
Humidification
HumDehumMode
Max. shift temperature
setpoint (P461)
P461 > 0 K
62 | 186
Applications with a 3-speed fan:
The external dehumidifier is controlled via external DC – On/Off converter
connected to analog output Y50. The output signal is DC 10 V if
dehumidification control is requested.
Output Y50 remains On for min. 30 seconds (not selectable).
This function is available without specific settings (P400, P401 and P402 are
not displayed).
The current of the external DC – On/Off converter cannot exceed the maximum
output current of Y50 (max. 5 mA). We recommend using the converter from Titan
(single relay control (IO/1RM) at 3 mA input current).
The function controls minimum relative humidity in the room and is available only
for applications with DC 0...10 V fan or no fan.
The external humidifier connected to the relay output is enabled as soon as
humidity drops below setpoint humidity low (P026) at hysteresis is ±5 %.
To enable the relay function, set P400 (output Q1), P401 (output Q2) or P402
(output Q3) to 8. The humidification S-Mode object sends On to the bus as soon as
the output is energized.
When humidity drops below the low setpoint or exceeds the high setpoint, symbol
is displayed and S-Mode object HumDehumMode sends the corresponding
state on the bus.
When humidity reaches setpoint humidity high (Comfort: P024, Economy: P025),
the thermostat shifts the temperature setpoint to reduce relative humidity in the
room.
The maximum shifting temperature setpoint can be set via P461 at Expert level at
a setting range of -3...3 K, depending on the connected equipment. The factory
setting is 3 K.
The maximum shifting temperature setpoint value is reached at setpoint humidity
high (P024, P025) +10%.
The positive values of P461 (0.5...3.0 K) are used for heating and cooling, or
heating in a humid cold environment.
For heating and cooling, both temperature setpoints (heating and cooling) are
shifted in parallel (i.e., dead zone remains unchanged).