6
Connection
Application examples
6.4.3 Swap function and/or fan in the 2nd stage
Example 1:
nd
Fan in the 2
stage
172 | 186
2-pipe fan coil application for floor heating/cooling (2-stage heating/cooling), fan
nd
runs only in the 2
stage:
Commissioning
●
Fan
●
Valve
●
Valve
See Technical data [➙ 177] for min. and
max. ratings
nd
P350 = 4 (2
stage)
P201 = 5 (floor)
P203 = 5 (fan coil unit)
Outputs used
●
M1
DC 0...10 V fan
●
V1
DC valve floor
●
V2
DC valve fan coil
units
RDG26..KN