Frost protection (P109)
A6V11545892_en--_e
IAQ control with On/Off damper: P453 = 2 or 3
If On/Off damper control is selected, the following parameters are available:
P453: Indoor air quality damper (2 = On/Off (normally open), 3 = On/Off
(normally closed))
P456: IAQ fan P-band Xp
P357, P353: Fan min. output
P359 & P360, P355: Fan max. output
The following graphics show the IAQ control by running the fan, in applications with
On/Off damper.
DC fan
W
IAQ setpoint (P023)
IAQ
Fan_min
Min. DC 0...10 V fan speed (P357)
The damper is fully open if CO
(P023).
The hysteresis of the damper is fixed at 100 ppm. The 3-speed fan switch off point
is 100 ppm below the switch on point.
In the dead zone (no H/C demand), the damper does not open, and fan does not
operate until CO
concentration reaches the IAQ setpoint.
2
On/Off damper can be connected directly to thermostat terminal Q3 or Y4 (see IAQ
- CO2 connection diagrams [➙ 167]) or controlled via S-Mode object 103: On/Off
damper demand.
Notes:
When On/Off damper is selected, the fan speed depends on the higher fan
request between temperature demand and IAQ demand.
For energizing the damper during IAQ demand, select "IAQ damper" P453 = 3
(normally close).
This logic can be inverted by selecting P453 = 2 (normally open).
Enable IAQ frost protection to protect the coils (set P109 frost setpoint) when fresh
air from outside is supplied to the equipment.
Frost protection closes the damper if the outside temperature value from the bus
(sent to RDG via e.g. LTE-mode, zone 31) is below the setpoint and open again if.
the outside temperature increases by 2K (hysteresis) above the setpoint.
Frost protection is not supported if the fan is disabled (P350 = 0) or the application
is set to 4-pipe with 6-port valve (H/C no fan). (RDG200KN, RDG260KN,
RDG200T, RDG260T)
1-speed/3-speed fan
IAQ fan Xp
IAQ damper P-band Xp (P456)
Max. DC 0...10 V fan speed (P359
Fan_max
for heating & P360 for cooling)
(IAQ) concentration is higher than the setpoint
2
4
Functions
Additional functions
75 | 186