One inverter in each phase:
Power Connection
N
L1
L2
L3
N
Load
L1
L2
L3
Communication Connection
WARNING: Do not connect the current sharing cable between the inverters which are in different phases.
Otherwise, it may damage the inverters.
5. LCD Setting and Display
Setting Program:
Program
Description
AC output mode
*This setting is able
to set up only when
the inverter is in
28
standby mode. Be
sure that on/off
switch is in "OFF"
status.
P1
Selectable option
Single:
Parallel:
43
P2
When the unit is operated alone, please select
"SIG" in program 28.
When the units are used in parallel for single
phase application, please select "PAL" in
program 28. Please refer to 5-1 for detailed
information.
P3