25
Record Fault code
Bulk charging voltage
26
(C.V voltage)
Floating charging voltage
27
Floating charging voltage
AC output mode
*This setting is able to set
up only when the inverter is
28
in standby mode. Be sure
that on/off switch is in
"OFF" status
Bypass enable (default)
Record enable
24V default setting: 28.2V
Default setting: 56.4V
If self-defined is selected in program 5, this program can be
set up. Setting range is 24.0V to 32V for 24V and 48.0V to
64.0V for 48V. Increment of each click is 0.1V.
24V default to 27.0V
48V default setting: 54.0V
If self-defined is selected in program 5, this program can be
set up. Setting range is 24.0V to 32V for 24Vl and 48.0V to
64.0V for 48V. Increment of each click is 0.1V.
Single:
Parallel:
L1 phase:
L2 phase:
18
If selected and no matter
power ON button is pressed
on or not, inverter can work
in bypass mode if utility is
available.
Record disable (default)
When the units are used in
parallel with single phase,
please select "PAL" in
program 28.
It is required to have at
least 3 inverters or
maximum 9 inverters to
support three-phase
equipment. It's required to
have at least one inverter in
each phase or it's up to four
inverters in one phase.
Please refers to 5-2 for
detailed information.
Please select "3P1" in
program 28 for the inverters
connected to L1 phase,
"3P2" in program 28 for the
inverters connected to L2
phase and "3P3" in program