Software specifications

The following table shows the specifications of MX MESInterface-R.
Item
Basic operation specification
Device memory input/output
specification
DB input/output specification
Variable input/output
specification
Data operation and processing
specification
External communication client
Security
Basic operation specification
Item
Job (number of
Maximum
settings)
Action (number of
Maximum
settings)
For one job
Trigger condition
For one job
Configuration
type
Event/condition
type
Condition
combination type
Trigger buffering
count
Time information
Time
handling (time
Daylight saving
*1
information)
time
Time zone
Ethernet
Connection
method
Number of
channels
Number of default
gateways
MES Interface
Number of pieces
Function
that can be
Configuration Tool
connected
simultaneously
2 SPECIFICATIONS
20
2.1 Performance Specifications
Description
Specification for the operation (job), startup condition for the job (trigger condition),
operation unit of a job (action), and network information.
Specification for the accessible target device types and access units (device tags).
Specification for the accessible databases, access units (access table/procedure,
access field/procedure argument), and buffering of output data (DB buffering) at the
time of disconnection.
Specification for user variables (local variables, global variables) which can be
defined freely, system variables to refer to system information, and data types of
variable.
Specification for the operation processing such as addition and subtraction.
Specification for the communication from an MES interface module to external
devices.
Specification for security.
Specification
RD81MES96N
64 jobs
1920 actions
30 actions
• Main processing: 20 actions
• Pre/post-processing: 10 actions
2 events/condition
• Single event
• Multiple events
• Condition combination event
• Precondition × Event
• Single handshake
• Multiple handshake
• Condition (value monitoring)
• Condition (period of time)
• Event (value changed)
• Event (fixed time)
• Event (fixed cycle) (timer interval/time interval)
• Event (module monitoring) (MES interface module/control CPU)
• OR combination
• AND combination
192 times (A value is cleared due to power interruption/reset/setting update.)
Acquired from a CPU module (CPU No.1 in a multiple CPU system).
IPv4
2 channels (CH1/CH2) (Note that they cannot be connected to a same network, and no routing function between
CH1 and CH2.)
1 (It can be registered only in CH1 or CH2.)
5 (Maximum number of connections to a single MES interface module)
Reference
Page 20 Basic operation
specification
Page 22 Device memory input/output
Page 23 DB input/output
Page 24 Variable input/output
Page 24 Data operation and
processing
Page 24 External communication
client
Page 24 Security
RD81MES96
• Single event
• Multiple events
• Condition combination event
• Precondition × Event
• Single handshake

Advertisement

Table of Contents
loading

Table of Contents