Specifications; Performance Specifications - Mitsubishi Electric GT15-J61BT13 User Manual

Got2000/got1000 series cc-link communication unit
Table of Contents

Advertisement

2. SPECIFICATIONS

2.1 Performance Specifications

The following is the performance specification of CC-Link communication unit.
The general specification of the CC-Link communication unit are the same as
those of the GOT.
For the general specifications of the GOT refer to the User's Manual for the GOT
1
used.
*
Item
CC-Link station type
Number of occupied stations
Maximum number of link
points per system
Number of link points per station
Number of link points per number of
occupied stations
Transmission speed
Max. transmission distance
Max. number of modules connected
Connection cable
Internal current consumption
(5VDC)
Weight
*1 When installing an extension unit on the CC-Link communication
unit, limit the maximum operating ambient temperature by
subtracting 5 degrees from operating ambient temperature of the
general specifications.
*2 Each of the I/O signals (RX, RY) occupies 16 points of a system
area within device points.
For more details on the I/O signals, refer to Section 3.1.
Remote I/O(RX, RY)*
Ver.2
Remote register(RWw)
mode
Remote register(RWr)
Remote I/O(RX, RY)*
Ver.1
Remote register(RWw)
mode
Remote register(RWr)
156kbps/625kbps/2.5Mbps/5Mbps/10Mbps
The max. number of modules connected depends on the
configuration of the CC-Link system to be used.
For more details on the max. number of modules
connected, refer to the CC-Link System Master-Local
Module User's Manual.
2
Specifications
Intelligent device station
May be selected between 1 and 4.
2
2
Refer to *3
Refer to *4
Depends on the transmission speed.
26
CC-Link dedicated cable
0.56A
0.18kg (0.40Ib)
8192 points
2048 points
2048 points
2048 points
256 points
256 points

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1d7m57

Table of Contents