3 SPECIFICATIONS
Address (Decimal)
4
Station No.16
5
Station No.32
6
Station No.48
7
Station No.64
0: Normal
1: Data link error
Address (Decimal)
8
Station No.16
9
Station No.32
10
Station No.48
11
Station No.64
0: No remote I/O Error identified
1: Remote I/O error identified
Bit
b0
Data link failure
b1
All stations failed
b2
Remote I/O error
b3
Error of station outside control range
b4
Point mode setting error
b5
Transmission speed setting error
b6
Switching during operation
b14 to b7
Vacant
b15
Hardware failure
3 - 7
(2) Information of faulty station (Buffer memory address 4 - 7: Un\G4 – 7)
The data link states of remote stations are stored in this area.
b15
b14
Station No.15
Station No.31
Station No.47
Station No.63
(3) Remote I/O error information (Buffer memory address 8 - 11:
Un\G8 – 11)
Information on remote I/O error of each remote station executing data link is
stored in this area.
For individual errors, see the related manual for the remote station.
b15
b14
Station No.15
Station No.31
Station No.47
Station No.63
(4) Detailed error information (Buffer memory address 16: Un\G16)
Detailed information on errors detected by the master station is stored in this
area. When an error is detected in a station outside the control range, b3 will be
latched. Writing "1" to this area (b3) clears the error information of the station.
Item
b13
to
Station No.14
to
Station No.3
Station No.30
to
Station No.19 Station No.18 Station No.17
Station No.46
to
Station No.35 Station No.34 Station No.33
Station No.62
to
Station No.51 Station No.50 Station No.49
b13
to
Station No.14
to
Station No.3
Station No.30
to
Station No.19 Station No.18 Station No.17
Station No.46
to
Station No.35 Station No.34 Station No.33
Station No.62
to
Station No.51 Station No.50 Station No.49
0: Data link normal
1: One or more faulty station in data link identified
0: One or more normal data link station identified
1: All stations are faulty
0: No remote I/O error
1: One or more faulty remote I/O station
0: No error
1: Remote station(s) set to the station number higher than the last
of refresh range
0: Normal
1: Point mode switch set outside valid range
0: Normal
1: Transmission speed setting switch set outside valid range
0: No switching
1: Switching identified
0: Normal
1: Failure identified by self-loopback test
MELSEC-Q
b2
b1
Station No.2
b2
b1
Station No.2
Contents
b0
Station No.1
b0
Station No.1