SUN2000-(8K, 10K)-LC0 Series
User Manual
Table 8-2 Common alarms and troubleshooting measures
Alarm ID
Alarm
Name
2001
String
Voltage
High
2002
DC Arc
Fault
2003
DC Arc
Fault
Issue 01 (2023-09-15)
Alarm
Possible Causes
Severity
Major
The PV array is not
properly configured.
Excessive PV modules are
connected in series to the
PV string, and therefore the
open-circuit voltage
exceeds the maximum
operating voltage of the
device.
Cause ID = 1, 2, 3
● 1: The PV1 input voltage
is high.
● 2: The PV2 input voltage
is high.
● 3: The PV3 input voltage
is high.
Major
The PV string power cables
arc or are in poor contact.
● Cause ID 1: PV1 DC arc
fault
● Cause ID 2: PV2 DC arc
fault
● Cause ID 3: PV3 DC arc
fault
Major
The PV string power cables
arc or are in poor contact.
(String-level precise
detection)
● Cause ID 1: PV string 1
● Cause ID 2: PV string 2
● Cause ID 3: PV string 3
Copyright © Huawei Digital Power Technologies Co., Ltd.
8 System Maintenance
Troubleshooting
Check the serial connection
configuration of the PV string
and ensure that the PV string
open-circuit voltage is not
greater than the maximum
operating voltage of the device.
After the PV array configuration
is corrected, the alarm
disappears.
Check whether the string cables
arc or are in poor contact.
Check whether the PV string
cables arc or are in poor contact.