Configuration
August 2023
5. Set the communication parameters:
6. Select the Enable Channel check box to activate the protocol channel.
7. Select OK to store the current configuration and close the configuration window.
3.2
Install Rosemount 2410 Tank Hub in WinSetup
The TankMaster WinSetup wizard is the recommended tool for installing the tank hub. The
installation wizard manages basic configuration of the tank hub.
Perform the following steps to start the installation wizard in TankMaster WinSetup:
Procedure
1. In the TankMaster WinSetup workspace window select the Devices folder.
2. Right click and select Install New or, from the Service menu, select the Devices/
14
Table 3-1: Communication Parameters
Port
Baud rate
Stop bits
Parity
Modem
Handshaking
Reply timeout
Retries
Description
Install New option. The Select Device window opens.
FBM
The COM port the FBM is
connected to
4800
1
None
FBM 2180
None
1000 ms
3
Text describing the configured
channel
Manual Supplement
00809-0800-2410
RS485 converter
The COM port the converter is
connected to
9600
1
None
RS-485
RTS/CTS
1000 ms
3
Text describing the configured
channel