Emerson Rosemount 2410 Instruction Manual page 24

Tank hub, sakura emulation
Hide thumbs Also See for Rosemount 2410:
Table of Contents

Advertisement

Optional configuration and settings
August 2023
Table 5-4: Holding Register Sakura_TempErrorConfig (1212)
Value
0
1
2
3
(1)
Note that the tank hub will use -300.0 °C to indicate invalid temperature (configurable
in holding register 6096).
Figure 5-3
to value 1. The tank hub will reply with the latest good temperature value.
Figure 5-3: Example: Holding Register Sakura_TempErrorConfig (1212) Set to Value 1
Table 5-5: User Defined Invalid Temperature Value
Input register
Emul_Temp_ErrVal_1_10_C
24
Definition
Default
Last Valid
Invalid Value
User Defined
shows an examplewhere holding register Sakura_TempErrorConfig (1212) is set
Register
number
1206
Description
The tank hub will reply with default temperature value
999.9 °C. It is recommended to keep the configuration as
Default.
The tank hub will reply with the last good temperature
value.
The tank hub will reply with the temperature value that
is present in the tank hub even if the temperature is
considered to be invalid.
(1)
The tank hub will reply with the temperature value
configured in holding register 1206 (see
Default
Description
value
0
User defined invalid temperature value in
1/10 °C.
Manual Supplement
00809-0800-2410
Table
5-5).
Emerson.com/Rosemount