Optional configuration and settings
August 2023
5.11 

Digital input

The K1 and K2 relay input status can be included in the Sakura V1 protocol response. The
digital input value is customized as shown in
Table 5-9: Digital Input Values
Value
30h
31h
32h
33h
Note
This function must be enabled by the MiscCtrl register status bit 6. See
5.12 

Pressure value

There are three pressure values in the Sakura V1 protocol: P1, P2, and P3. They are by
default configured as:
P1: Liquid pressure
P2: Middle pressure
P3: Vapor pressure
For backward compatibility with Rosemount Rex, the Liquid pressure value can be
remapped to P2 and/or P3. This is done in holding register Sakura_PressConf (1214). If
Liquid pressure is remapped, Vapor pressure will be used for the other pressure requests
that are not remapped.
Table 5-10: Holding Register 1214, Bit Configuration
Bit 2,
P3_Liquid
0
0
0
0
1
1
1
1
30
Decoded
Description
ASCII char
0
K1 and K2 energized (or function disabled by holding register
MiscCtrl bit 6, see
1
K1 de-energized and K2 energized
2
K1 energized and K2 de-energized
3
K1 and K2 de-energized
Bit 1,
Bit 0,
Pressure values
P2_Liquid
P1_Liquid
0
0
Default: P1 = Liquid pressure, P2 = Middle pressure and P3 =
Vapor pressure
0
1
P1 = Liquid pressure, P2 = Middle pressure and P3 = Vapor
pressure
1
0
P2 = Liquid pressure, P1 = P3 = Vapor pressure
1
1
P1 = P2 = Liquid pressure, P3 = Vapor pressure
0
0
P3 = Liquid pressure, P1 = P2 = Vapor pressure
0
1
P1 = P3 = Liquid pressure, P2 = Vapor pressure
1
0
P2 = P3 = Liquid pressure, P1 = Vapor pressure
1
1
P1 = P2 = P3 = Liquid pressure.
Table
5-9.
Table
5-6)
Emerson.com/Rosemount
Manual Supplement
00809-0800-2410