Invalid Level Measurements - Emerson Rosemount 2410 Instruction Manual

Tank hub, sakura emulation
Hide thumbs Also See for Rosemount 2410:
Table of Contents

Advertisement

Optional configuration and settings
August 2023
Figure 5-1: Example: Holding Register Sakura_BaudRate (1217) Set to Value 0
Note
The baud rate value is only updated after restart or if the Sakura bus is idle for at least 60
seconds.
5.6 

Invalid level measurements

The tank hub reply on the Sakura host level request can be customized if the level value is
invalid.
Use holding register Sakura_LevelErrorConfig (1211) to customize your reply configuration,
see
Table
Table 5-2: Holding Register Sakura_LevelErrorConfig 1211
Value
0
1
2
3
Figure 5-2
to value 0. The tank hub will reply with the default level value 99999.9 mm.
22
5-2. This configuration is applicable on all tank positions.
Value definition
Default
Last Valid
Invalid Value
User Defined
shows an example where holding register Sakura_TempErrorConfig (1211) is set
Description
The tank hub will reply with the default level value 99999.9
mm. It is recommended to keep the configuration as Default.
The tank hub will reply with the last good level value.
The tank hub will reply with the level value that is present in
the tank hub even if the level is considered to be invalid.
The tank hub will reply will level value configured in holding
registers 1204 and 1205 (see
Manual Supplement
00809-0800-2410
Table
5-3).
Emerson.com/Rosemount