Note: 1. To save the energy, please remove the batteries when the device is not in use.
2. Please check the device verification information on the gateway or consult your platform server provider.
Low Voltage Warning
Low Voltage

5. Data Report

The device will immediately send a version packet report along with two uplink packets including current value (mA).
The device sends data in the default configuration before any configuration is done.
Default setting:
Max Interval = 0x708 (1800s)
Min Interval = 0x708 (1800s)
ReportChange= 0x0064 (100 mA)
Note: (1) Min Interval < 30s → Data reported every 30 seconds
(2) Max Interval < Min Interval → Data reported at Min Interval
(3) Frequent changes of current may cause inaccurate results when the device is sampling (15 seconds before the
beginning of the Min Interval).
Measurement Range and Accuracy:
Note: (1) R718N1(E), R718N13(E), and R718N17(E): report data as 0A when the current < 0.1A .
(2) R718N115(E), R718N125(E), R718N163(E), and R718N1100(E):
report data as 0A when the current < 1A .
Please refer Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver
http://www.netvox.com.cn:8888/cmddoc
3.2V
(MinTime cannot be less than 30 seconds. MaxTime must be greater than MinTime.)
Device
CT
R718N1(E)
Solid-Core
R718N13(E)
Clamp-on
R718N17(E)
Clamp-on
R718N115(E)
Clamp-on
R718N125(E)
Clamp-on
R718N163(E)
Clamp-on
R718N1100(E)
Clamp-on
to resolve uplink data.
Measurement Range
100mA – 30A
100mA – 30A
100mA – 75A
1A – 150A
1A – 250A
5A – 630A
10A – 1000A
5
Accuracy
±1%