5. Data Report

When the device is turned on, it will immediately send a version package and a report data with ADC sampling voltage and voltage
value. Before any configuration, the device sends data according to the default configuration.
Data will be reported once per 15 minutes by default setting.
Default setting:
Maximum time: 0x0384 (900s)
Minimum time: 0x0384 (900s)
Battery Voltage Change: 0x01 (0.1V)
ADC Raw Value Change: 0x0064 (100mV)
Note:
1. The device report interval will be programmed based on the default firmware which may vary.
2. The interval between two reports must be the minimum time.
3. Please refer Netvox LoRaWAN Application Command document and Netvox LoRa Command Resolver
http://cmddoc.netvoxcloud.com/cmddoc
Data report configuration and sending period are as following:
Min. Interval
(Unit:second)
Any number between
1~65535

5.1 Example of ReportDataCmd

FPort:0x06
Bytes
1
Version
Version– 1 byte –0x01——the Version of NetvoxLoRaWAN Application Command Version
DeviceType– 1 byte – Device Type of Device
The devicetype is listed in Netvox LoRaWAN Application Devicetype doc
ReportType – 1 byte –the presentation of the NetvoxPayLoadData,according the devicetype
NetvoxPayLoadData– Fixed bytes (Fixed =8bytes)
Device
Device Type
R718IA
0x20
to resolve uplink data.
Max. Interval
(Unit:second)
Any number between
1~65535
1
1
DeviceType
ReportType
Report Type
0x01
(1Byte, unit:0.1V)
Reportable Change
Can not be 0.
NetvoxPayLoadData
Battery
ADCRawValue
(2Bytes,unit:1mv)
5
Current Change≥
Reportable Change
Report
per Min. Interval
Var(Fix=8 Bytes)
NetvoxPayLoadData
(5Bytes,fixed 0x00)
Current Change<
Reportable Change
Report
per Max. Interval
Reserved